Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2012 | ELECTRIC - INTERMEDIATE | Approved | ||
| 03/02/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
| 03/01/2012 | ELECTRIC - INTERMEDIATE | Partial Approval | chiller 1 & 2 vfd chwp 1,2,3 cntrl vfd's for 2 absorbtion chiller pumps |
|
| 11/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PREVIOUS ITEMS |
|
| 11/04/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO TEMP ENERGIZE CHILLER AFTER CORRECTIONS 2) BUSHINGS PER 352.46 & 300.4 3) TIGHTEN LOOSE FITTINGS 4) BOND JUNCTION BOX ENCLOSURE |