Permit: T11CM02343

Parcel: 14029003H

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T11CM02343

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/04/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
10/19/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) RESTROOM #118 & #119 CLOSET FLANGES OK
10/13/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PRESLAB COMPRESSOR AREA OK
2) RESTROOMS 106 & 107 CLOSET FLANGES OK
10/11/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DWV AMD WATER RESTRPP, 149 & 150, SHOWERS 166 & 167 EXCEPT SHOWER VALVES. WATER TEST FLOOR SINK THRU ROOF AT COMPRESSOR AREA OK PROVIDE TRACER WIRE PRIOR TO BACKFILL
09/21/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WATER TEST DWV THRU ROOF RESTROOM AREA 118 AND 119 WITH WATER DISTRIBUTION IN WALL & OVER HEAD
2) INSULATION IN WALL AND OVER HEAD RESTROOM 106, 107, 118 & 119 OK
09/20/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DWV THRU ROOF 118,119 AND ROOM 117 WITH WATER & INSULATION IN WALL
09/19/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) WATER DISTRIBUTION IN WALL OK TO INSULATE
2) PROVIDE DWV TEST THRU ROOF, 106, 107. 118 AND 119 ONLY
08/29/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) DWV THRU TO 4" ABOVE REVENT 10' AFF RESTROOM 106 & 107 WATER TEST, INCLUDING P-6 B
2) DWV THRU REVENT TO 4" 10' AFF RESTROOM FEMALE 1128 AND MALE 119 INCLUDING P-4 AND P-6A, EXCEPT LAVS IN 119 RE-TEST
08/24/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
SOUGH EAST AIR & VAC TO ABOVE CEILING