Permit: T11CM02341

Parcel: 141146100

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/26/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/18/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE AN OVERFLOW SENSOR
2) EXTEND VENT IN CONDENSATE DRAIN ABOVE THE DRAIN PAN
3) METAL SLEEVE CONNECTED TO EXISTING DUCT IS NOT CONNECTED PROPERLY, THERE ARE NO SCREWS AND TAPE IN NOT STICKING
4) PROVIDE A PROTECTIVE CAOTING ON EXPOSED ARMAFLEX AND REMOVE ANY DUCT TAPE USED OUTDOORS ON THE LINE SET