Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/18/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE AN OVERFLOW SENSOR 2) EXTEND VENT IN CONDENSATE DRAIN ABOVE THE DRAIN PAN 3) METAL SLEEVE CONNECTED TO EXISTING DUCT IS NOT CONNECTED PROPERLY, THERE ARE NO SCREWS AND TAPE IN NOT STICKING 4) PROVIDE A PROTECTIVE CAOTING ON EXPOSED ARMAFLEX AND REMOVE ANY DUCT TAPE USED OUTDOORS ON THE LINE SET |