Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/08/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) OVERFLOW SENSOR CANNOT BE INSTALLED IN THE PRIMARY DRAIN WHEN THERE IS A SECONDARY OUTLET PROVIDED |
|
| 08/03/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE THE REQUIRED OVERFLOW SENSOR 2) EXTEND VENT IN CONDENSATE DRAIN ABOVE DRAIN PAN 3) PVC MUST BE MINIMUM 6" FROM SINGLE WALL VENT 4) EXTEND FURNACE VENT MINIMUM 3' ABOVE COMBUSTION AIR INTAKE ON ROOF 5) PROVIDE THE REQUIRED STRUCTURAL DRAWING APPROVED BY CITY OF TUCSON |
|
| 07/28/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO LADDER PROVIDED |