Permit: T11CM02338

Parcel: 110061860


Addresses:

4185 E GLENN ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/16/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/08/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) OVERFLOW SENSOR CANNOT BE INSTALLED IN THE PRIMARY DRAIN WHEN THERE IS A SECONDARY OUTLET PROVIDED
08/03/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE THE REQUIRED OVERFLOW SENSOR
2) EXTEND VENT IN CONDENSATE DRAIN ABOVE DRAIN PAN
3) PVC MUST BE MINIMUM 6" FROM SINGLE WALL VENT
4) EXTEND FURNACE VENT MINIMUM 3' ABOVE COMBUSTION AIR INTAKE ON ROOF
5) PROVIDE THE REQUIRED STRUCTURAL DRAWING APPROVED BY CITY OF TUCSON
07/28/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO LADDER PROVIDED