Inspection Status: Not ready for Inspection
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T11CM02316
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Not ready for Inspection
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/15/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
08/11/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PURPLE ROOM 105 INSTALL R.A. INTO HALLWAY AS PER PLANS 2) FINISH SUPPLY TERMINATIONS 3) PROVIDE BEADED COLLARS AT CEILING DIFFUSERS 4) CONDENSATE CANNOT TERMINATE ONTO PAVEMENT 5) PROVIDE FRESH AIR INTAKES 6) PROVIDE AIR BALANCE REPORT 7) SEE BLDG INSPECTOR FOR TCO |
|
08/10/2011 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |