Permit: T11CM02290

Parcel: 12710017D

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T11CM02290

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/20/2011 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
10/18/2011 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INSULATE AND SUPPORT ABOVE CEILING
2) RECALL FOR DEMO
10/14/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) ABS NOT READ
2) PEX TUBING NOT SECURED AND NOT INSULATED
10/13/2011 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) DO NOT USE A HOSE WITHOUT A VACUUM BREAKER TO FILL DWV
2) A BLAKE TEE MAY BE INSTALLED HORIZONTALLY
3) A CLEANOUT SHALL OPEN ABOVE FLOW LEVEL
4) PROVIDE A TEST AND STRAP & SECURE ALL PIPING
5) OK TO INSULATE TUBING
6) IECC CODE REQUIRES 1" THICK INSULATION ON ALL RECIRCULATING HOT PIPING
7) PLAN SPECIFIES LAV CARRIERS