Inspection History Details
Inspection Status: Approved
Inspection History: OUTDOOR LIGHTING FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2012 | OUTDOOR LIGHTING FINAL | Approved | IVRS - Inspection :* | |
| 07/13/2012 | OUTDOOR LIGHTING FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/05/2012 | OUTDOOR LIGHTING FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOXES MORE THAN 1/4" BOX TO SURFACE 314.20 2. PANEL LABELING NOT LEDGEABLE 408.4 3. PLEASE PROVIDE INSTRUCTIONS FOR INSTA HOT TO VERIFY COLD + PLUG LISTING 4. MISSING NIGHT LIGHT NORTH HALL 5. PANELS + CIRCUITS NOT AS PER PLANS WHERE IS PANEL "N"? 6. OUTDOOR LIGHTNING NOT AS PER PLANS 7. PLEASE OPEN ROOM ON SOUTH END |
|
| 05/01/2012 | OUTDOOR LIGHTING FINAL | Not ready for Inspection | IVRS - Inspection :* 1) 4-104 MAIN BREAKER TO BE AMPACITY FOR CONDUCTOR 2) GEC TO TERMINATE TO GROUNDED BAR |
|
| 04/04/2012 | OUTDOOR LIGHTING FINAL | Not ready for Inspection | IVRS - Inspection :* |