Permit: T11CM02288

Parcel: 12217365A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/18/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/13/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
REVISED PLAN NEED CITY STAMP
07/05/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOXES MORE THAN 1/4" BOX TO SURFACE 314.20
2. PANEL LABELING NOT LEDGEABLE 408.4
3. PLEASE PROVIDE INSTRUCTIONS FOR INSTA HOT TO VERIFY COLD + PLUG LISTING
4. MISSING NIGHT LIGHT NORTH HALL
5. PANELS + CIRCUITS NOT AS PER PLANS WHERE IS PANEL "N"?
6. OUTDOOR LIGHTNING NOT AS PER PLANS
7. PLEASE OPEN ROOM ON SOUTH END
05/17/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/16/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUB PANEL COVERS OPEN TO BE CLOSED UP FOR POWER
05/09/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE ELECTRICIAN FINISH WORK BEFORE RECALLING FOR INSPECTION
05/08/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
05/01/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/04/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*