Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T11CM02279

Parcel: 133231390

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM02279

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/15/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE A CANVAS COVER OVER NEW DUCT WORK CONNECTION
2) CONENSATE DRAINS ON 2 EXISTING UNITS RUNS UPHILL
3) PROVIDE ROOF JACKS AT NEW CONDENSATE PENETRATIONS THRU ROOF
4) PROVIDE FILTERS FOR ? AIR INTAKES AND A/C UNITS FOR EXISTING UNITS
11/14/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE ACCESS TO ROOF
2) PROVIDE LETTER FROM ENGINEER TO ELIMINATE ECONOMIZERS FOR EXISTING RTU'S