Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/28/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
09/26/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROPER CRIMP TOOL IS REQUIRED FOR SINGLE WALL VENT CONNECTIONS. REMOVE ALL TAPE
2) PROVIDE APPROVED PIPING FOR RELIEF DRAIN-FLEX NOT ALLOWED
3) REMOVE OR PROTECT PIPE INSULATIN WITHIN 6" OF VENT
4) GAS FLEX IS STRETCHED TO TIGHT
5) SEDIMENT TRAP REQUIRED TO A MINIMUM OF 3"
6) REMOVE EXCESS FLUX FROM SOLDIER JOINTS
7) SECURE TUBING IN ATTIC-MAX 32"