Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T11CM02249
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2011 | FIRE - FINAL | Approved | ||
09/13/2011 | FIRE - FINAL | Partial Approval | Received a sprinkler report showing deficiencies need to check the following areas: 1. Connect pre-action to alarm panel 2. No coverage in room next to elect. room north wall 3. Sprinkler head needs to be lowered Southeast conference room 4. Phone lines to fire alarm dialer disconnected? 5. Old computer room not protected by the sprinkler system? |
|
08/25/2011 | FIRE - FINAL | Partial Approval | 1. ok for temp c of o per tucson fire. 2. rooms 117 a&b. 115,105 A&b. |