Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T11CM02245
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/27/2011 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
09/13/2011 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) COMPLETE ALL ITEMS FROM 8/30/11 INSPECTION 2) MET CHRIS FROM VALLEY WIDE SOLAR FOR DISCUSSION ON SITE. PLEASE PROVIDE LISTING FOR THIS TYPE PIPING FLASHING USE ON TILE |
|
08/30/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) HAVE YOUR INSTALLER ON SITE FOR NEXT INSPECTION 2) HAVE THE TILE ROOF INSTALLATION INSTRUCTIONS ON SITE 3) ALL FLASHINGS TO BE PROPERLY INSTALLED 4) PANEL SUPPORTS OR PANEL STRUCTURE SUPPORTS TO BE INTO BLDG STRUCTURE 5) HOLDOWN STRAP CAPS TO BE WEATHER TIGHT 6) BROKEN TILES TO BE REPLACED 7) TILES TO SIT FLAT AND CORRECTLY INSTALLED |
|
08/19/2011 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/21/2011 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE A PROTECTION BARRIER FOR AUTO IMPACT AND TANK 2) PROVIDE LADDER ACCESS TO ROOF TOP PANEL 3) PROVIDE MINIMUM 6" CLEARANCE FROM SINGLE WALL VENT AND COMBUSTIBLE MATERIALS LIST NOT COMPLETE |