Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
11/08/2011 BUILDING - FINAL Approved IVRS - Inspection :*
11/04/2011 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CALLED 623-975-2313 OFFICE CLOSED ON FRIDAY
2) NO ONE HOME FOR ACCESS
3) PLEASE RECALL
11/01/2011 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) OK ITEMS #1, 2, 4 & 5
2) NEED TO CONSULT ITEM #3 WITH SUPERVISOR AND CODE OFFICIAL. WILL RETURN CALL TO LALO AT SALT RIVER SOLAR
10/27/2011 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FINISH PROTECTION AT PANEL #8 COPPER
2) VERIFY CONNECTION OF RAIL BONDING TO EQUIPMENT BOND CONDUCTOR
3) OK BOTTOM FLASHING INSTALL TOP FLASHING ON TILES
4) PV CABLES NOT SUPPORTED UP UNDER PANELS
5) SUPPORT FLEX CONDUIT IN ATTIC PER CODE INTERVALS
10/26/2011 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PHYSICAL PROTECTION FOR #8 GROUNDING ELECTRODE CONDUCTOR
2) SECURE PV CABLE UNDER MODULES
3) ONLY ONE CONDUCTOR TO LUG TERMINAL
4) PROVIDE ACCESS TO VIEW ATTIC