Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
| 07/15/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EXTEND VENT IN CONDENSATE DRAIN ABOVE DRAIN PAN 2) CONDENSATE CANNOT TERMINATE INTO TEH T & P DRAIN 3) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTOR-REMOVE TAPE 4) BLANK OFF BOTTOM OF EVAP. COIL WITH SHEET METAL, NOT TAPE |