Permit: T11CM02217

Parcel: 12209003A


Addresses:

3911 E PIMA ST


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T11CM02217

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2011 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
08/18/2011 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REVISION FOR SOIL PIPING IS NOT ACCURATE OR AS ILLUSTRATED ON YOUR RED LINES
2) P-4,P-5,P-3 AND P-1 ARE ALL ON ONE 2" WASTE
3) THE 4" EXISTING DRAIN DOES NOT EXIST IN THIS LOCATION
08/10/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) JANITOR LAUNDRY AND BR INSTALLED PER RED LINES-PROVIDE REVISION AND COVER AT YOUR RISK
2) INSTALL BACKING AT MS
3) INSTALL PIPE INSULATION
4) ADD SUPPORTS OVER HEAD
08/05/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) WORK AREA SINKS SOIL PIPE TO REVENT ABOVE CEILING
2) DWV AND WATER IN WALLS
08/03/2011 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE MINIMUM 2 PERCENT SLOPE
2) RED LINE CHANGE OF ROUTING
3) COMPLETE WORK AT TRS
4) INSULATE AND SECURE PIPING IN WALLS