Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T11CM02217
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2011 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
08/18/2011 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REVISION FOR SOIL PIPING IS NOT ACCURATE OR AS ILLUSTRATED ON YOUR RED LINES 2) P-4,P-5,P-3 AND P-1 ARE ALL ON ONE 2" WASTE 3) THE 4" EXISTING DRAIN DOES NOT EXIST IN THIS LOCATION |
|
08/10/2011 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) JANITOR LAUNDRY AND BR INSTALLED PER RED LINES-PROVIDE REVISION AND COVER AT YOUR RISK 2) INSTALL BACKING AT MS 3) INSTALL PIPE INSULATION 4) ADD SUPPORTS OVER HEAD |
|
08/05/2011 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1) WORK AREA SINKS SOIL PIPE TO REVENT ABOVE CEILING 2) DWV AND WATER IN WALLS |
|
08/03/2011 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE MINIMUM 2 PERCENT SLOPE 2) RED LINE CHANGE OF ROUTING 3) COMPLETE WORK AT TRS 4) INSULATE AND SECURE PIPING IN WALLS |