Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/21/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS ON LIST NOT TAKEN CARE OF, PLEASE CORRECT THEM 2) ON ROOF CANNOT USE SHALLOW STRUT 3) ON ROOF PANEL ABOVE A/C DISCONNECT LOOSE 4) IS THERE A PANEL MISSING ON ROOF ? MICRO INVERTER THERE BUT PANEL MISSING. GROUND TO BE LANDED ON LUG NOT COILED AROUND LEG STAND 5) STRAP PIPE AT SERVICE AND GOING UP TO ROOF |
|
| 09/29/2011 | ELECTRIC - FINAL | Denied | IBC/IRC 106.4 WORK HAS NOT BEEN INSTALLED IN ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS. 1) NEC 230.17 -MAIN DISCONNEDCT MISSING IN PANEL 2) NEC 690.64 -50 AMP SOLAR BREAKER IN PANEL OVERSIZED 3) NEC 250.64 -GROUNDING ELECTRODE MISSING BONDING 4) NEC 690 -IDENTIFYING LABELS MISSING ON PANELS 5) RECALL FOR ROOFTOP INSPECTION. PLEASE PROVIDE SUITABLE LADDER TO ACCESS ROOF -IBC 109.1,IRC 109.3 |