Permit: T11CM02171

Parcel: 12904157A


Addresses:

2121 E BROADWAY BL


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T11CM02171

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
10/03/2011 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) MET JACOB ON SITE, NO CITY APPROVED PLANS OR PERMIT ON SITE. WENT OVER COMMON PROBLEMS WITH INSTALLATION
2) T & P DRAIN TO BE PIPED
3) ELECTRIC WATER HEATER REQUIRES 25 AMP OVER CURRENT PROTECTION PER MANUFACTURER
4) SUPPORT ALL PIPING AT CORRECT INTERVALS
5) INSULATION TO BE SEALED PER MANUFACTURE INSTALLATION INSTRUCTIONS
6) GROUND WIRE TO BE GREEN OR NO INSULATION
7) DRYWALL AT CEILING TO BE SEALED
8) PROVIDE LISTING FOR SHARK BITE FITTINGS USED ON 240 DEGREE WATER GLYCOL SYSTEM
9) INSTALL TEMPERING VALVES
10) PROVIDE LISTING FOR ROOF ? IN PLACE OF ROOF FLASHINGS FOR PIPE PENETRATIONS
11) PRESSURE RELIEF TO TERMINATE DOWNWARD TO AVOID SCALDING WITH NO THREADED ENDS AT TERMINATION
12) LIST NOT COMPLETE