Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T11CM02171
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
10/03/2011 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) MET JACOB ON SITE, NO CITY APPROVED PLANS OR PERMIT ON SITE. WENT OVER COMMON PROBLEMS WITH INSTALLATION 2) T & P DRAIN TO BE PIPED 3) ELECTRIC WATER HEATER REQUIRES 25 AMP OVER CURRENT PROTECTION PER MANUFACTURER 4) SUPPORT ALL PIPING AT CORRECT INTERVALS 5) INSULATION TO BE SEALED PER MANUFACTURE INSTALLATION INSTRUCTIONS 6) GROUND WIRE TO BE GREEN OR NO INSULATION 7) DRYWALL AT CEILING TO BE SEALED 8) PROVIDE LISTING FOR SHARK BITE FITTINGS USED ON 240 DEGREE WATER GLYCOL SYSTEM 9) INSTALL TEMPERING VALVES 10) PROVIDE LISTING FOR ROOF ? IN PLACE OF ROOF FLASHINGS FOR PIPE PENETRATIONS 11) PRESSURE RELIEF TO TERMINATE DOWNWARD TO AVOID SCALDING WITH NO THREADED ENDS AT TERMINATION 12) LIST NOT COMPLETE |