Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/17/2012 | PLUMBING - PROGRESS | Approved | IVRS - Inspection :* | |
| 01/26/2012 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* | |
| 12/14/2011 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* 1) VENTS REQUIRE UV PROTECTION AND CLEARANCE 2) ISOLATE CU FROM GRID WIRES 3) OVERHEAD DWV REQUIRES SUPPORT AT EACH CHANGE OF DIRECTION, NOT EXCEED 4', CU SUPPORTS NOT TO EXCEED 6' 4) PROVIDE LISTED CLEANOUT PLUGS FOR SCREWS 5) TRAP ARM MAY NOT CHANGE ELEVATION 6) VACUUM RELIEF VAVLE SHOWN 7) EAST PLAN REVISION OK |
|
| 12/09/2011 | PLUMBING - PROGRESS | Not ready for Inspection | IVRS - Inspection :* |