Permit: T11CM02109

Parcel: 105110690

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T11CM02109

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/27/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/23/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
AIR BALANCE REPORT OK
1) CONDENSATE NOT TERMINATED PROPERLY
2) PROVIDE ACCESS TO GREASE DUCT FOR CLEANING
12/15/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1ST INSPECTION OF THE DAY:
1) HP-5 NOT WIRED CORRECTLY ON D.S.D.
2) HP-4 NOT WIRED CORRECTLY ON D.S.D.
3) HP-6 NOT WIRED CORRECTLY ON D.S.D.
4) HP-2 AND HP-3 OK
5) HP-1 NOT OPERATIONAL
6) NOT READY FOR TEMP C OF O
1) ALL DUCT SMOKE DETECTORS TEST OK
2) OUTSIDE AIR HAS BEEN SET TO MINIMUM INTAKE REQUIREMENTS, AWAITING BALANCE REPORT
3) NO OTHER LIFE SAFETY ISSUES OBSERVED, SEE BLDG INSPECTOR FOR TEMP C OF O
4) AFTER HOURS INSPECTION PAID WITH CHECK #11698 WAS RECEIVED IN THE AMOUNT OF $165.00 WRITTEN OUT TO CITY OF TUCSON
12/14/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) HOODS OK FOR FIRE INSPECTION
2) NEED DUCT SMOKE DETECTOR TEST AND AIR BALANCE REPORT
12/13/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
12/09/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*