Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2011 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 12/13/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CAPTURE AND CONTAINMENT TEST OK 2) LARGE HOOD IS MISSING 2 MAKE UP AIR DUCTS 3) PROVIDE AIR BALANCE AND DUCT SMOKE DETECTOR REPORT 4) FIRE WRAP OK |
|
| 12/05/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK FOR CEILING TILES FOR MECHANICAL |
|
| 12/02/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SEAL ALL DUCT ABOVE T-BAR 2) PROVIDE SESMIC TO MAINS |
|
| 11/14/2011 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 11/08/2011 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SEAL ALL DUCT JOINTS PER I.E.C.C. 2) PROVIDE MINIMUM 3 SCREWS IN STRAPS PER SMACNA 3) OK TO ROCK HARD LIDS-MECH ONLY 4) PROVIDE FLEX CONNECTORS AT ALL RTU'S |