Permit: T11CM02109

Parcel: 105110690

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T11CM02109

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/14/2011 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
12/13/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CAPTURE AND CONTAINMENT TEST OK
2) LARGE HOOD IS MISSING 2 MAKE UP AIR DUCTS
3) PROVIDE AIR BALANCE AND DUCT SMOKE DETECTOR REPORT
4) FIRE WRAP OK
12/05/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK FOR CEILING TILES FOR MECHANICAL
12/02/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SEAL ALL DUCT ABOVE T-BAR
2) PROVIDE SESMIC TO MAINS
11/14/2011 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/08/2011 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) SEAL ALL DUCT JOINTS PER I.E.C.C.
2) PROVIDE MINIMUM 3 SCREWS IN STRAPS PER SMACNA
3) OK TO ROCK HARD LIDS-MECH ONLY
4) PROVIDE FLEX CONNECTORS AT ALL RTU'S