Permit: T11CM02109

Parcel: 105110690

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T11CM02109

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2011 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
10/19/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) GAS UNDER SLAB OK
2) INTERCEPTOR NOT FULL
3) SEWER-NO TEST
4) VENT FITTINGS BELOW FLOOD RIM TO BE DAINAGE TY
10/12/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) CORRECTIONS MADE, NEED LETTER AND LAST SECTION OF PIPING LEAVING BLDG
2) CALL FOR PRE-SLAB PRIOR TO CONCRETE
10/11/2011 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1) MARK WITH JJC, BEN WITH ON THE SIDE
2) PROVIDE DOCUMENTATION FOR ALL CHANGES TO PLAN SPECS
3) INSTALL TEST FITTINGS IN THE PROPER DIRECTION OF FLOW (PVC SPECIFIED)
4) POINT OF VENT SHALL BE ABOVE THE CENTER LINE OF THE DRAIN SERVED
5) PROVIDE MINIMUM TRAP ARM DISTANCES
6) PROVIDE A WYE ? FITTING ON ISLAND LOOP VENT