Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM02109
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/08/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) BOXES MORE THAN 1/4" 314.20-CANNOT USE DRYWALL SCREW TO MOUNT DEVICES 2) EQUIPMENT TO BE LISTED AND LABELED 3) LABEL PANEL DIRECTORY PER 408.4 4) CONDUCTOR TO BE IN RACEWAY FOR WALK IN-SEAL WITH NON COMBUSTIBLE PRODUCT 5) CHECK ROOF NEXT TIME |
|
12/05/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) JUNCTION BOX ACCESS ABOVE PANEL 2) FINISH VDV 3) ALL EQUIPMENT TO BE LISTED AND LABELED 4) OK TO TILE AFTER CORRECTION AND OK ON FINAL |
|
12/02/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT VDV CABLING PER 725.8, 800.24, 300.11 AND 815.24 2) M/C CABLE TO BE IDENPENDENTLY SUPPORTED 300.11-NOT OFF OF OTHER WIRING METHODS 3) SUPPORT M/C WITHIN 12" OF BOXES + 6' 4) SUPPORT CONDUIT WITHIN 3' OF BOXES + 10 5) VERIFY BOX FILL |
|
11/02/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
11/01/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |