Permit: T11CM02109

Parcel: 105110690

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM02109

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
12/09/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/08/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
11/02/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK STUD FRAME WALLS AND SOFFITS FOR CANS
2) OK 2" PVC FEEDER CONDUIT
3) FINISH BAR
11/01/2011 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROTECT M/C CABLE AT SHALLOW STUDS AND CENTER OF STUD CHANNELS, ALSO TOP PLATE
2) USE PROPER SUPPORTS TO SECURE M/C CABLE
3) SECURE M/C CABLES WITHIN 12" OF RECESSED CANS
4) ATTACH SUPPORT WIRES BOTH ENDS 300.11
5) VERIFY DERATING 310.15 AT SWITCH BANK
6) PROTECT PVC AT BASE PLATES
7) NEED LETTER AUTHORIZING USE OF M/C CABLE
8) INDOOR PVC COVERED WITHOUT INSPECTIONS