Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM02109
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/09/2011 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
11/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
11/02/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK STUD FRAME WALLS AND SOFFITS FOR CANS 2) OK 2" PVC FEEDER CONDUIT 3) FINISH BAR |
|
11/01/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROTECT M/C CABLE AT SHALLOW STUDS AND CENTER OF STUD CHANNELS, ALSO TOP PLATE 2) USE PROPER SUPPORTS TO SECURE M/C CABLE 3) SECURE M/C CABLES WITHIN 12" OF RECESSED CANS 4) ATTACH SUPPORT WIRES BOTH ENDS 300.11 5) VERIFY DERATING 310.15 AT SWITCH BANK 6) PROTECT PVC AT BASE PLATES 7) NEED LETTER AUTHORIZING USE OF M/C CABLE 8) INDOOR PVC COVERED WITHOUT INSPECTIONS |