Permit: T11CM02091

Parcel: 116182260


Addresses:

937 W CONGRESS ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/28/2013 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/18/2013 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/18/2013 ELECTRIC - FINAL Denied 1. SEE NOTES LAST INSPECTION. INSTALL BOND BUSHING IN SUB-PANEL
2. WATER HTR MISSING DISC SW OR LOCKOUT ON CIRCUIT BREAKER
3. SUB-PANEL ABOVE SMALL SINK NOT SHOWN ON PLAN OR IDENTIFIED
4. REPAIR & SUPPORT CONDUITS/BOXES OUTSIDE & INSIDE BLD SHOULD BE RAIN TIGHT OUTDOORS
5. WIRE ON WATER HTR CIRCUIT BREAKER OVERHEATED - REPLACE AS NECESSARY
6. INSTALL ROOF JACKS AT ROOF PENETRATIONS
7. PLAN SHOWS 60 AMP CKT BRKR FOR SUB-PANEL, SEE ONE LINE DIAGRAM