Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/18/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/18/2013 | ELECTRIC - FINAL | Denied | 1. SEE NOTES LAST INSPECTION. INSTALL BOND BUSHING IN SUB-PANEL 2. WATER HTR MISSING DISC SW OR LOCKOUT ON CIRCUIT BREAKER 3. SUB-PANEL ABOVE SMALL SINK NOT SHOWN ON PLAN OR IDENTIFIED 4. REPAIR & SUPPORT CONDUITS/BOXES OUTSIDE & INSIDE BLD SHOULD BE RAIN TIGHT OUTDOORS 5. WIRE ON WATER HTR CIRCUIT BREAKER OVERHEATED - REPLACE AS NECESSARY 6. INSTALL ROOF JACKS AT ROOF PENETRATIONS 7. PLAN SHOWS 60 AMP CKT BRKR FOR SUB-PANEL, SEE ONE LINE DIAGRAM |