Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/12/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/07/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) PAPERWORK STATES LABELING TO BE VISIBLE-PLEASE VERIFY LOCATION |
|
| 09/29/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) NEED NEUTRAL FIELD EVALUATION PAPERWORK FOR CT SCAN |
|
| 09/09/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VERIFY LISTING AND LABELING OF EQUIPMENT CT SCAN 2) CONTRACTOR TO MAINTAIN LOCK OUT/TAG OUT 3) OK LAST ITEM CORRECTIONS |
|
| 09/08/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) BOND JUMPERS PER 250.66 2) NEUTRAL REQUIRED TO DISCONNECT |
|
| 08/24/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK LISTED SPLICE COUPLING | |
| 08/23/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OKAY LAST 10' TO BUILDING WILL NEED LISTED CONDUIT REBAR RT FOR 2" PVC |
|
| 08/22/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | OK 2- 4" TEP UNDER ASPHALT TO BUILDING PVC CONDUITS | |
| 08/19/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 08/17/2011 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 08/16/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) NOTE: EXISTING ELECTRIC TO MEET REQUIREMENTS OF 517.13 FOR USE 2) PROTECT M/C CABLE INSIDE STUD CHANNEL 3) OK ROOM 101-103 |