Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/14/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LOOSE EXTERIOR RAILING ON ROOF 2) NEED BACK FLOW PREVENTER ON ROOF HOSE BIB 3) NEED CONTINUOUS HANDRAIL AT WINDER 4) CANNOT NICK ALUMINUM WHEN STRIPPING WIRE 5) MAIN NEUTRAL LOOSE 6) H2O HEATER CONDUIT LOOSE 7) NO POXWALL SCREWS IN COVER PLATES 8) INSTALL ARC SHEILD AT L.R. OUTLET 7) NO POXWALL SCREWS IN COVER PLATES |