Permit: T11CM02023

Parcel: 129064620


Addresses:

2626 E 21ST ST


Inspection Status: Approved

Inspection History: BUILDING - PROGRESS

Permit Number - T11CM02023

Inspection Description - BUILDING - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
08/16/2011 BUILDING - PROGRESS Approved IVRS - Inspection :*
08/05/2011 BUILDING - PROGRESS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SERVICE DROP LACKS REQUIRED 7' CLEARANCE FROM AZ ROOM FLAT ROOF
2) EXPOSE RAFTER CONNECTIONS AZ ROOM AT BEARING WALLS
3) PER CODE AZ ROOM REQUIRES HEAT. WHAT IS HEAT SOURCE-NOT ON PLAN
4) ELECTRICAL IN AZ ROOM NOT TO CODE, EXPOSED ROMEX UNDER 7' LAKCS PROTECTION FROM PHYSICAL DAMAGE. LIGHTS NOT WIRED TO CODE
5) EXPOSE ALL BEARING HEADERS TO VERIFY SIZE AZ ROOM
6) PORIVDE LETTERHEAD FROM LICENSED ELECTRICAL CONTRACTOR STATING ALL ELECTRICAL BOTH ROOMS DONE WITHOUT INSPECTION IS TO CODE AND FOR SAFETY DOES NOT POSE A HAZARD OR EXPOSE ALL ELECTRICAL FOR INSPECTION
7) MISSING OUTLETS PER CODE