Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM02021
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/23/2012 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/03/2011 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS AND STILL NEED MILL WORK |
|
08/02/2011 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) MC CANNOT BE LESS THAN 1 1/4" FROM FACE OF STUD 300 NEC 2) LV CABLING TO BE SUPPORTED PER 725-800 NEC 3) NOT READY IN OTHER AREAS 4) RECALL WHEN READY |