Permit: T11CM02010

Parcel: 11306139B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T11CM02010

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/02/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/02/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) SEAL OUTSIDE LIGHT FOR WET LOCATION
2) CLEAN SURFACE UNDER GROUND BARS 250.12
3) FILL UNUSED OPENING TOP OF MAIN DISCONNECT
4) WORK INSTALLAED FOR SERVICE NOT REFLECTIVE OF PLANS-NEED REVISION
5) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL
6) BOXES MORE THAN 1/4" 314.20
7) LIGHTING TO BE PER 410.63 (G)
8) LIGHTING NOT REFLECTIVE OF PLANS
08/01/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*