Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11CM02010
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/02/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/02/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SEAL OUTSIDE LIGHT FOR WET LOCATION 2) CLEAN SURFACE UNDER GROUND BARS 250.12 3) FILL UNUSED OPENING TOP OF MAIN DISCONNECT 4) WORK INSTALLAED FOR SERVICE NOT REFLECTIVE OF PLANS-NEED REVISION 5) CLEAN EXCESS DIRT AND FOREIGN MATERIAL FROM BOTTOM OF PANEL 6) BOXES MORE THAN 1/4" 314.20 7) LIGHTING TO BE PER 410.63 (G) 8) LIGHTING NOT REFLECTIVE OF PLANS |
|
08/01/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |