Permit: T11CM02007

Parcel: 10408093B


Addresses:

625 W AUTO MALL DR

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
12/07/2011 ELECTRIC - UFER Approved IVRS - Inspection :*
11/21/2011 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BOXES AND WIRING METHODS 5' FROM OPENING TO BE IN CLASSIFIED AREA AND FILL UNUSED OPENINGS
2) SUPPORT RACEWAY 3' OF LB
3) FILL UNUSED OPENING AT SWITCHBOARD
4) LABEL BREAKER
11/14/2011 ELECTRIC - UFER Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
11/10/2011 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT M/C AND FLEX WITHIN 12" OF FITTINGS AND 6' INTERVALS
2) LABEL DISCONNECTING MEANS
3) TIGHTEN LOOSE FITTINGS
4) CANNOT USE CORDS AS WIRING METHOD 400.7 & 8
5) BOND JUCTION BOX ENCLOSURE
6) NEED ELECTRICIAN PRESENT
7) UNITS IN OPERATION WITHOUT CLEARANCES