Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2011 | ELECTRIC - UFER | Approved | IVRS - Inspection :* | |
| 11/21/2011 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOXES AND WIRING METHODS 5' FROM OPENING TO BE IN CLASSIFIED AREA AND FILL UNUSED OPENINGS 2) SUPPORT RACEWAY 3' OF LB 3) FILL UNUSED OPENING AT SWITCHBOARD 4) LABEL BREAKER |
|
| 11/14/2011 | ELECTRIC - UFER | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED |
|
| 11/10/2011 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT M/C AND FLEX WITHIN 12" OF FITTINGS AND 6' INTERVALS 2) LABEL DISCONNECTING MEANS 3) TIGHTEN LOOSE FITTINGS 4) CANNOT USE CORDS AS WIRING METHOD 400.7 & 8 5) BOND JUCTION BOX ENCLOSURE 6) NEED ELECTRICIAN PRESENT 7) UNITS IN OPERATION WITHOUT CLEARANCES |