Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/12/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FLEX COPPER NOT ALLOWED IN A T & P DRAIN 2) FURNACE VENT CONNECTOR MUST CONNECT INTO BOTTOM OF TEE AND WATER HEATER INTO SIDE OF TEE 3) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTORS 4) PROVIDE A COATING ON ALL EXPOSED ARMAFLEX 5) CONDENSOR OVERFUSED 6) COPPER TUBING NOT TO BE USED AS A REPLACEMENT FOR FUSES IN DISCONNECT AT SERVICE |