Permit: T11CM01987

Parcel: 127020410


Addresses:

5302 E 3RD ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/19/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
07/12/2011 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FLEX COPPER NOT ALLOWED IN A T & P DRAIN
2) FURNACE VENT CONNECTOR MUST CONNECT INTO BOTTOM OF TEE AND WATER HEATER INTO SIDE OF TEE
3) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS OF VENT CONNECTORS
4) PROVIDE A COATING ON ALL EXPOSED ARMAFLEX
5) CONDENSOR OVERFUSED
6) COPPER TUBING NOT TO BE USED AS A REPLACEMENT FOR FUSES IN DISCONNECT AT SERVICE