Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/29/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WHITE WIRE NOT TO BE USED AS HOT LEG 2) LINE SETS NOT INSTALLED ON ROOF, INSULATION IS TO BE COATED TO PROTECT FROM U.V. 3) T-STAT WIRE TO BE PROTECTED ON ROOF 4) ELECTRIC CONDUIT TO BE BLOCKED UP OFF ROOF 5) PROVIDE GRUMMETS WHERE LINE SETS ENTER COIL 6) INSULATE LINE SETS INDOORS 7) PROVIDE SECONDARY DRAIN AT INDOOR COIL |