Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T11CM01977
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/11/2011 | FRAMING | Approved | IVRS - Inspection :* | |
09/30/2011 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES FOR BOTH UNITS: 1) LOOSE FITTING ON BOTTOM OF PANEL 2) PANELS AND MAINS TO BE RATED AT 22K AIC-SEE NOTE ON PLAN 3) 1-HOLE STRAPS NOT PER LISTING-SHOULD NOT BE A GAP BETWEEN RACEWAY AND STRUCTURE |
|
09/21/2011 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |