Permit: T11CM01964

Parcel: 136012470


Addresses:

8088 E SNAKEROOT DR


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T11CM01964

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/11/2011 PLUMBING - FINAL Approved IVRS - Inspection :*
07/11/2011 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE 6" MINIMUM CLEARANCE FROM COMBUSTIBLES AND SINGLE WALL VENT CONNECTOR
2) SUPPORT ALL PIPING AT CORRECT INTERVALS
3) PROVIDE PROTECTION BARRIER FOR TANK FROM AUTO IMPACT
4) J-HOOKS CANNOT BE DRIVEN THRU ROOF SURFACE FOR TUBING SECURING