Permit: T11CM01952

Parcel: 12510025E


Addresses:

3566 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T11CM01952

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/29/2012 ELECTRIC - INTERMEDIATE Approved
03/02/2012 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) NED STAMPED REVISION
02/29/2012 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CLEAN EXCESS FOREIGN MATERIAL AND DIRT FROM BOTTOM OF ELECTRICAL EQUIPMENT
2) PLANS CALL FOR GROUND RODS-NOT INSTALLED
3) INSPECTION FOR CONCRETE ENCASED NOT DONE BY THIS DEPT.
4) PLAN REVISIONS TO HAVE CITY STAMP
12/28/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) PROTECT ENDS OF VDV RACEWAYS FROM SHARP METAL EDGES
2) SUPPORT VDV CABLES IN WALLS 725.8
3) OK WALLS AFTER CORRECTIONS