Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/18/2011 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/17/2011 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 11/15/2011 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE ABS COMBOS-INSTALL PVC AS SPECIFIED 2) PROVIDE 1/4" PER FOOT SLOPE ON DRAIN PIPING 3) BACKFLOW ASSEMBLY IS SPECIFIED FOR COOLERS ONLY, NOT FOR OTHER WATER PIPING. PROVIDE TEST REPORT AFTER CORRECTING INSTALLATION 4) CORRECT LINE SIZE AS SHOWN ON YOUR PLAN 5) REMOVE EXCESS FLUX FROM COPPER JOINTS, ALL JOINTS SHALL BE DEBURRIED AS REQUIRED BY CODE 6) FAILURE TO COMPLY MAY RESULT IN REINSPECTION FEES |
|
| 11/10/2011 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |