Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2011 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/23/2011 | PLUMBING - FINAL | Not ready for Inspection | HORIZONTAL PVC MAY NOT BE INSTALLED ABOVE GRADE. IRR BACKFLOW ASSEMBLY IS NOT PER PLAN SPEC ALSO PROVIDE CERT AFTER CORRECTION. LAV CARRIERS SPECIFIED MIXING VALVE NOT PER PLAN SPEC WATER DISPENSER NOT INSTALLED PAINT PVC PAN DRAW TERMINATION HOSE BIBS NOT PER SPEC PROVIDE DOCUMENTATION FOR ALL CHANGES |