Permit: T11CM01884

Parcel: 10510010D


Addresses:

333 E WETMORE RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T11CM01884

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/06/2012 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/05/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
TRANSFER SWITCH:
1) MULTIPLE CONDUCTORS ON LUG LISTED FOR 1 CONDUCTOR
2) VERIFY 250.8 FOR SCREW ATTACHMENT
01/04/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MAINTAIN WORKING CLEARANCE AT GENERATOR DISCONNECT
2) NEED EQUIPMENT UNLOCKED
3) TIGHTEN LOOSE GROUND LUGS ON BUSHINGS