Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM01867
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/16/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
08/15/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY LISTING AND LABELING OF EQUIPMENT AS STAMPED ON PLANS 2) MISSING SCREWS AT RECEPT COVERS 406.3 3) CANNOT USE SHEETMETAL THREAD SCREWS FOR GROUNDING 250.8 4) VERIFY DERATING OF CONDUCTORS 310.15 5) RETERMINATE "A" PHASE LINE AND LOAD AT 60 AMP DISCONNECT 7) BOX MORE THAN 1/4" 314.20 AND USE APPROVED HARDWARE NOT DRYWALL SCREWS 8) CABINET OUTLET TO BE ACCESSIBLE |
|
07/26/2011 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |