Permit: T11CM01858

Parcel: 11703321C


Addresses:

400 E UNIVERSITY BL

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
11/03/2011 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/02/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) FIXTURE CLIPS TO BE EFFECTIVE
2) VDV 725.3
3) CAP UNUSED CONDUIT OPENINGS
4) LABEL DISCONNECTS
5) BOX OVERFILLED
6) NOTE: 314.20 LIGHTS
10/31/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) HARD LIDS ROOM #004
2) 035 CEILING OK
10/26/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
2) LABEL DISCONNECTS
3) OK LIDS HALL 012, STORAGE 016
10/11/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK HARD LIDS #35, 19 THRU 24 AND CORRIDOR 028 & 014
09/23/2011 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/19/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) JUNCTION BOXES TO BE ACCESSIBLE
2) SUPPORT AND SECURE M/C CABLES 12" + 6' 334.30
3) USE APPROVED M/C CABLE STRAPS
4) USE APPROVED CONDUIT STRAPS 408.3
5) TIE WIRE ON HORIZONTALS ONLY
09/16/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
09/15/2011 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*