Permit: T11CM01847

Parcel: 126171140


Addresses:

3922 E MONTECITO ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
07/21/2011 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
06/29/2011 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LINE VOLTAGE POWER CORDS PENETRATING CABINETS ARE TO HAVE A CLAMP TYPE CONNECTOR, PLASTIC BUSHINGS NOT APPROVED FOR THIS APPLICATION
2) CONDENSATE PIPING IS TO BE RE-LOCATED SO AS TO PROVIDE CLEAR OPENING AT FURNACE ACCESS DOOR
3) T-STAT WIRE ON EXTERIOR IS TO BE SHIELDED FROM DAMAGE BY USE OF CONDUIT OR OTHER APPROVED MEANS
4) REFRIDGERATION PIPE INSULATION EXPOSED TO DAYLIGHT IS TO BE COATED TO PROVIDE U.V. PROTECTION
5) CONDENSATE TO 90 DEGREE AWAY FROM STRUCTURE