Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2011 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/29/2011 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LINE VOLTAGE POWER CORDS PENETRATING CABINETS ARE TO HAVE A CLAMP TYPE CONNECTOR, PLASTIC BUSHINGS NOT APPROVED FOR THIS APPLICATION 2) CONDENSATE PIPING IS TO BE RE-LOCATED SO AS TO PROVIDE CLEAR OPENING AT FURNACE ACCESS DOOR 3) T-STAT WIRE ON EXTERIOR IS TO BE SHIELDED FROM DAMAGE BY USE OF CONDUIT OR OTHER APPROVED MEANS 4) REFRIDGERATION PIPE INSULATION EXPOSED TO DAYLIGHT IS TO BE COATED TO PROVIDE U.V. PROTECTION 5) CONDENSATE TO 90 DEGREE AWAY FROM STRUCTURE |