Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 08/16/2011 | ELECTRIC - ABOVE CEILING | Approved | ||
| 08/08/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) EMT TO BE REMOVED AND WIRE 2) LOW VOLTAGE TO BE STRAPPED AND OFF GRID CEILING 3) BOXES MISSING KO SEALS 4) PIPE AND BOXES TO BE STRAPPED FROM CEILING TO GRID 5) LOW VOLTAGE PIPES MISSING BUSHINGS |