Permit: T11CM01762

Parcel: 125060240


Addresses:

1941 E 4TH ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
08/31/2012 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
08/29/2012 PLUMBING - INTERMEDIATE Partial Approval 1. Flange OK. 2. 11/2" stub for lavatory OK. 3. Shower liner has ponding, and won't drain completly.
08/28/2012 PLUMBING - INTERMEDIATE Partial Approval 1. Install 2"x11/2" bushing at lav. waste and stub out 11/2". Install tile under the closet flange. 2. Open the weep holes at the shower drain and test to the threshold.
07/11/2012 PLUMBING - INTERMEDIATE Not ready for Inspection 1. Plumbing intermediate is going to be reopened. 2 Secure the closet flange to the finished floor. 3. Call for shower pan inspection- refer to the hand out. Call for inspection when tyhe installer can be present. 4. Remove the 2" stub out for the lavatory, and install a one and a half inch bushing with an inch and a half stub out. 5. Missing screw on sheet rock.