Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
Permit Number - T11CM01756
Inspection Description - MECHANICAL - FINAL
Inspection Status - Partial Approval
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2011 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* THE LIQUID LINE FILTER DRIER IS INSTALLED IN REVERSE. SIGHT GLASS NOT RUNNING CLEAR. PROVIDE A PROTECTIVE COATING, ON EXPOSE ARMFLEX AT CONDENSOR. OK TO BACKFILL ELEC. MAXINE RAMIER OWNER |