Permit: T11CM01717

Parcel: 136334270


Addresses:

3010 S BROWN AV

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/14/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/09/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) 3/8" I.D. X 3' GAS FLEX NOT ADEQUATE FOR 110,000 BTU FURNACE
2) DO NOT USE A DBL WALL FITTING ON FURNACE THEN INTO SINGLE WALL
3) REMOVE ALL FOIL TAPE
4) EXTEND VENT CONDENSATE DRAIN HIGHER AND TERMINATE CONDENSATE INTO RAIN GUTTER
5) BLOCK AND CLAMP EVERY 4'
6) PROVIDE THE REQUIRED GFI SERVICE RECEPT