Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T11CM01715
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/26/2012 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* OK POLE BASES, UG. ELECTRIC. | |
12/14/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1.1" 20 FOR LITING IN TRENCH NORTH WEST CORNER PARKING LOT OK 2. 3 MORE LITE POLES 200' OF PVC IN TRENCH SAME NORTH WEST PARKING LOT OK |
|
12/13/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
12/11/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
11/27/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK PULL BOX TO PULL BOX CORNER W/ATT CHANNEL | |
11/14/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK PVC BY SWITCH GEAR DS-02 | |
10/29/2012 | ELECTRIC - UNDERGROUND | Partial Approval | 4 PED LIGHTS AT EMERGENCY ENTRANCE | |
10/15/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK PVC & 10 LV GROUND LIGHTS EAST EAST SIDE MONUMENT SIGN OK IMC TO BACK OF MONUMENT |
|
10/11/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK 10 LOW VOLTAGE GROUND LIGHTS AND RACEWAYS WEST SIDE MONUMENT SIGN. | |
10/10/2012 | ELECTRIC - UNDERGROUND | Cancelled | IVRS - RI canceled | |
10/05/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK 8 POLES AS MARKED OK LOW VOLTAGE IN GROUND LIGHTS AND RACEWAYS CANS FOUNDERS GARDEN |
|
10/02/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK AS MARKED | |
09/28/2012 | ELECTRIC - UNDERGROUND | Not ready for Inspection | NOT READY CANCELLED | |
09/27/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK PVC AS MARKED OKO ONE POLE BASE | |
09/26/2012 | ELECTRIC - UNDERGROUND | Partial Approval | LIFTING UNDER GROUND AS PER PLAN | |
09/21/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK 3 POLE BASE NORTH EAST SIDE OK TO ECAST 4-4 PVC | |
09/19/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
08/08/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK PVC CONDUITS AS MARKED OR POLES AND POLE BOXES LOT 19 | |
08/02/2012 | ELECTRIC - UNDERGROUND | Partial Approval | OK 4 POLE BASES INCLUDING ON WYATT OR PVC AS MARKED | |
08/01/2012 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
07/31/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
07/24/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
07/20/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
07/18/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* GROUND POLES AS DISCUSSED OK 1" PVC FOR LIGHTING AT SIGN AS MARKED TO PULL BOXES |
|
07/11/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
07/10/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
07/09/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
07/05/2012 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
07/03/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
07/02/2012 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* OKAY PVC CONDUITS AS MARKED ON JOB PLANS |
|
06/29/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
06/28/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
06/26/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK TO COVER AT TMC D501 OK TO ENERGIZE DMC DS-01 AFTER HOURS INSPECTION FEE PAID AT OFFICE |
|
06/25/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK DS-03 CONNECTIONS OK 90 DEGREE STUD INTO J-2 CABINET CMC-DF01 |
|
05/24/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) COMMUNICATIONS ABOVE CONCRETE PIPES SOUTH OF NEW BLDG AND EST OF PARKING GARAGE OK |
|
05/23/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 50' OF 4" PVC IN TRENCH INCASED IN CONCRETE OK |
|
05/22/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 5-4" PVC PIPE CONTINUES IN DITCH SOUTH OF NEW BLDG OK |
|
05/21/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 100' OF 5-4" PVC IN TRENCH OK |
|
05/18/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* TRENCH SOUTH OF NEW BUILDING OK |
|
05/17/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 110' OF 5-4" PVC IN TRENCH SOUTH NEW BLDG AND EAST OF PARKING LOT OK |
|
05/01/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 8 LIGHT POLES AND CAGES BETWEEN LAUNDRY AND NAVAJO ALL OK |
|
04/26/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 8 LIGHT POLES WITH 8 PULL BOXES NEXT TO EACH LIGHT FOR NAVAJO TO LAUNDRY PARKING LOT |
|
04/18/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 2 LITE POLES SOUTH OF PARKING GARAGE GROUND BOXES & GROUNDING OK |
|
03/26/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) INCASED BOTH CONDUITS IN CONCRETE OK, FROM SWITCH GEAR AT GARAGE TO TRANSFORMER |
|
03/16/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 2 POLE BASES NORTH OF GARAGE OK |
|
03/12/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 15 POLE BASE AND ? REBAR OK |
|
03/08/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) LAST POLE ERICKSON BLDG |
|
02/23/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) SWITCH GEAR GROUNDING AND PVC IN TRENCH OK FOR NAVAJO & APACHE BLDG |
|
02/14/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 190 FT PVC PRIMARY NORTH OF PARKING GARAGE IN TRENCH CASED IN CONCRETE OK 2) DS01 THRU DS03 AND DS01E THRU DS03E SWITH GEARS TO TRANSFORMER OK |
|
02/09/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* PRIMARY AT PARKING GARAGE PVC IN DITCH OK |
|
01/25/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) FROM TMC 65 TO DS-01 TMC PIPE TO LAUNDRY TRENCH OK |
|
01/19/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) PRIMARY WEST SIDE OF PARKING GARAGE IN CASED IN CONCRETE OK |
|
01/18/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) TRANSFORMER GROUND RING 2 GROUNDS 2' DEEP |
|
01/10/2012 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) PVC STUBS FOR TRANSFORMER A & B OK |
|
12/20/2011 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
12/20/2011 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
12/16/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 2-4" PVC WEST PAVILLION ELECTRICAL ROOM TO DISTRIBUTION #3 AND GROUND RING 3/0 WIRE WITH 4 GROUND RODS |
|
12/13/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 3-4" PVC SOUTH OF LAUNDRY 100' OK |
|
12/07/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) EAST OF PARKING GARAGE AND SOUTH OF LAUNDRY 4" PVC IN TRENCH POWER 100' INCREASED IN CONCRETE AND COMMUNICATIONS ON TOP OK |
|
12/02/2011 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
12/01/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) TRANSFER TO SWITCH GEAR STUBS OK |
|
11/30/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) DISTRIBUTION #2 WEST TO EXISTING COMMUNICATION VAULT-APPROX 200' |
|
11/15/2011 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
11/10/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 2-4" ACROSS ROAD SOUTH OF LAUNDRY BLDG OK |
|
11/09/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) ENCASED 4" CONDUIT LINES SOUTH OF LAUNDRY |
|
11/08/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 2 55' OF 4" PVC LINES-SOUTH OF LAUNDRY AREA OK TO COVER |
|
11/02/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 70' OF 2" PVC SOUTH OF LAUNDRY IN TRENCH OK |
|
10/31/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 4" PVC STUBS SOUTH OF LAUNDRY IN TRENCH OK-FROM SOUTH TO LAUNDRY ACROSS ROAD 4" PVC IN TRENCH OK |
|
10/28/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 90' OF 4-4" PVC WEST OF LAUNDRY IN TRENCH OK |
|
10/27/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 80' 5-4" PVC SOUTH OF LAUNDRY OK |
|
10/26/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
10/25/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) PIPES AT SES ALL OK |
|
10/24/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) COMMUNICATION, EM POWER AND REGULAR POWER IN DITCH AT SWITCH AREA OK 2) NORTH OF LAUNDRY 4-4" IN DITCH 100' PVC OK |
|
10/21/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 4-4" PVC TO SWITCH GEAR LOCATION OK |
|
10/20/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
10/18/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) TRENCH UP TO PARKING LOT 13 4-4" PVC OK |
|
10/17/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 200' ACROSS ROAD 4-4" PVC IN DITCH FROM ALAMO TO LAUNDRY BLDG OK |
|
10/14/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 130' 4-4" PVC IN TRENCH ACROSS THE ROAD SOUTH OF ALAMO BLDG OK |
|
10/12/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) PIPE RUN OF 4-4" IN FRONT OF ALAMO OK |
|
10/11/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 80' 4-4" PVC POWER AND COMMUNICATIONS IN TRENCH IN FRONT OF ELAMO OK |
|
10/07/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) 1-3/4" FOR LIGHT POLE, 100' OF 4-4" IN DITCH ELAMO OK |
|
10/06/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. 120' PVC 4.4" IN FRONT OF ELAMO IN TRENCH OK 2. #9 PARKING LOT LITING 1.3 IN & OUT OK |
|
10/04/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* CHECKED PRINT + CONSULTED ELECTRICAL CONTRACTOR ON WORK TO BE DONE |
|
09/01/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
08/29/2011 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) UNDERGROUND FROM TRANSFORMER TO BLDG OK |