Permit: T11CM01715

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T11CM01715

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
12/26/2012 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :* OK POLE BASES, UG. ELECTRIC.
12/14/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1.1" 20 FOR LITING IN TRENCH NORTH WEST CORNER PARKING LOT OK
2. 3 MORE LITE POLES 200' OF PVC IN TRENCH SAME NORTH WEST PARKING LOT OK
12/13/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
12/11/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
11/27/2012 ELECTRIC - UNDERGROUND Partial Approval OK PULL BOX TO PULL BOX CORNER W/ATT CHANNEL
11/14/2012 ELECTRIC - UNDERGROUND Partial Approval OK PVC BY SWITCH GEAR DS-02
10/29/2012 ELECTRIC - UNDERGROUND Partial Approval 4 PED LIGHTS AT EMERGENCY ENTRANCE
10/15/2012 ELECTRIC - UNDERGROUND Partial Approval OK PVC & 10 LV GROUND LIGHTS EAST EAST SIDE MONUMENT SIGN
OK IMC TO BACK OF MONUMENT
10/11/2012 ELECTRIC - UNDERGROUND Partial Approval OK 10 LOW VOLTAGE GROUND LIGHTS AND RACEWAYS WEST SIDE MONUMENT SIGN.
10/10/2012 ELECTRIC - UNDERGROUND Cancelled IVRS - RI canceled
10/05/2012 ELECTRIC - UNDERGROUND Partial Approval OK 8 POLES AS MARKED
OK LOW VOLTAGE IN GROUND LIGHTS AND RACEWAYS CANS FOUNDERS GARDEN
10/02/2012 ELECTRIC - UNDERGROUND Partial Approval OK AS MARKED
09/28/2012 ELECTRIC - UNDERGROUND Not ready for Inspection NOT READY CANCELLED
09/27/2012 ELECTRIC - UNDERGROUND Partial Approval OK PVC AS MARKED OKO ONE POLE BASE
09/26/2012 ELECTRIC - UNDERGROUND Partial Approval LIFTING UNDER GROUND AS PER PLAN
09/21/2012 ELECTRIC - UNDERGROUND Partial Approval OK 3 POLE BASE NORTH EAST SIDE OK TO ECAST 4-4 PVC
09/19/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
08/08/2012 ELECTRIC - UNDERGROUND Partial Approval OK PVC CONDUITS AS MARKED OR POLES AND POLE BOXES LOT 19
08/02/2012 ELECTRIC - UNDERGROUND Partial Approval OK 4 POLE BASES INCLUDING ON WYATT OR PVC AS MARKED
08/01/2012 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
07/31/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/24/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/20/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/18/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
GROUND POLES AS DISCUSSED
OK 1" PVC FOR LIGHTING AT SIGN AS MARKED TO PULL BOXES
07/11/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/10/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/09/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/05/2012 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
07/03/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/02/2012 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
OKAY PVC CONDUITS AS MARKED ON JOB PLANS
06/29/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
06/28/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
06/26/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK TO COVER AT TMC D501
OK TO ENERGIZE DMC DS-01
AFTER HOURS INSPECTION FEE PAID AT OFFICE
06/25/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK DS-03 CONNECTIONS
OK 90 DEGREE STUD INTO J-2 CABINET CMC-DF01
05/24/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) COMMUNICATIONS ABOVE CONCRETE PIPES SOUTH OF NEW BLDG AND EST OF PARKING GARAGE OK
05/23/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 50' OF 4" PVC IN TRENCH INCASED IN CONCRETE OK
05/22/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 5-4" PVC PIPE CONTINUES IN DITCH SOUTH OF NEW BLDG OK
05/21/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 100' OF 5-4" PVC IN TRENCH OK
05/18/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
TRENCH SOUTH OF NEW BUILDING OK
05/17/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 110' OF 5-4" PVC IN TRENCH SOUTH NEW BLDG AND EAST OF PARKING LOT OK
05/01/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 8 LIGHT POLES AND CAGES BETWEEN LAUNDRY AND NAVAJO ALL OK
04/26/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 8 LIGHT POLES WITH 8 PULL BOXES NEXT TO EACH LIGHT FOR NAVAJO TO LAUNDRY PARKING LOT
04/18/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
2 LITE POLES SOUTH OF PARKING GARAGE GROUND BOXES & GROUNDING OK
03/26/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) INCASED BOTH CONDUITS IN CONCRETE OK, FROM SWITCH GEAR AT GARAGE TO TRANSFORMER
03/16/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 2 POLE BASES NORTH OF GARAGE OK
03/12/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 15 POLE BASE AND ? REBAR OK
03/08/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) LAST POLE ERICKSON BLDG
02/23/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) SWITCH GEAR GROUNDING AND PVC IN TRENCH OK FOR NAVAJO & APACHE BLDG
02/14/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 190 FT PVC PRIMARY NORTH OF PARKING GARAGE IN TRENCH CASED IN CONCRETE OK
2) DS01 THRU DS03 AND DS01E THRU DS03E SWITH GEARS TO TRANSFORMER OK
02/09/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
PRIMARY AT PARKING GARAGE PVC IN DITCH OK
01/25/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) FROM TMC 65 TO DS-01 TMC PIPE TO LAUNDRY TRENCH OK
01/19/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) PRIMARY WEST SIDE OF PARKING GARAGE IN CASED IN CONCRETE OK
01/18/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) TRANSFORMER GROUND RING 2 GROUNDS 2' DEEP
01/10/2012 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) PVC STUBS FOR TRANSFORMER A & B OK
12/20/2011 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
12/20/2011 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
There is no access to the site.| 920*
12/16/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 2-4" PVC WEST PAVILLION ELECTRICAL ROOM TO DISTRIBUTION #3 AND GROUND RING 3/0 WIRE WITH 4 GROUND RODS
12/13/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 3-4" PVC SOUTH OF LAUNDRY 100' OK
12/07/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) EAST OF PARKING GARAGE AND SOUTH OF LAUNDRY 4" PVC IN TRENCH POWER 100' INCREASED IN CONCRETE AND COMMUNICATIONS ON TOP OK
12/02/2011 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
12/01/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) TRANSFER TO SWITCH GEAR STUBS OK
11/30/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) DISTRIBUTION #2 WEST TO EXISTING COMMUNICATION VAULT-APPROX 200'
11/15/2011 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
11/10/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 2-4" ACROSS ROAD SOUTH OF LAUNDRY BLDG OK
11/09/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) ENCASED 4" CONDUIT LINES SOUTH OF LAUNDRY
11/08/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 2 55' OF 4" PVC LINES-SOUTH OF LAUNDRY AREA OK TO COVER
11/02/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 70' OF 2" PVC SOUTH OF LAUNDRY IN TRENCH OK
10/31/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 4" PVC STUBS SOUTH OF LAUNDRY IN TRENCH OK-FROM SOUTH TO LAUNDRY ACROSS ROAD 4" PVC IN TRENCH OK
10/28/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 90' OF 4-4" PVC WEST OF LAUNDRY IN TRENCH OK
10/27/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 80' 5-4" PVC SOUTH OF LAUNDRY OK
10/26/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
10/25/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) PIPES AT SES ALL OK
10/24/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) COMMUNICATION, EM POWER AND REGULAR POWER IN DITCH AT SWITCH AREA OK
2) NORTH OF LAUNDRY 4-4" IN DITCH 100' PVC OK
10/21/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 4-4" PVC TO SWITCH GEAR LOCATION OK
10/20/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
10/18/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) TRENCH UP TO PARKING LOT 13 4-4" PVC OK
10/17/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 200' ACROSS ROAD 4-4" PVC IN DITCH FROM ALAMO TO LAUNDRY BLDG OK
10/14/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 130' 4-4" PVC IN TRENCH ACROSS THE ROAD SOUTH OF ALAMO BLDG OK
10/12/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) PIPE RUN OF 4-4" IN FRONT OF ALAMO OK
10/11/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 80' 4-4" PVC POWER AND COMMUNICATIONS IN TRENCH IN FRONT OF ELAMO OK
10/07/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) 1-3/4" FOR LIGHT POLE, 100' OF 4-4" IN DITCH ELAMO OK
10/06/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. 120' PVC 4.4" IN FRONT OF ELAMO IN TRENCH OK
2. #9 PARKING LOT LITING 1.3 IN & OUT OK
10/04/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
CHECKED PRINT + CONSULTED ELECTRICAL CONTRACTOR ON WORK TO BE DONE
09/01/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
08/29/2011 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1) UNDERGROUND FROM TRANSFORMER TO BLDG OK