Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T11CM01711

Parcel: 140290410

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/23/2011 MECHANICAL - FINAL Approved IVRS - Inspection :*
09/21/2011 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
08/31/2011 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) DUCT WORK IN SERVER ROOM NOT TO BE SUSPENDED BY GRID WIRE AND PROVIDE STRAPS PER SMACNA
2) PROVIDE AIR BALANCE REPORT
3) NEED TO INSPECT ROOF TOP UNITS