Permit: T11CM01711

Parcel: 140290410

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/26/2011 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/25/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) SUPPORT MC 12" & 6' PER NEC, EMT WITHIN 3' PER NEC
08/19/2011 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELED PER CONTRACTOR
08/05/2011 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LV CABLING TO BE SUPPORTED 725-800 NEC
2) 2 X 4 AND ANY LAY IN FIXTURES NEED TO BE SECURED TO GRID 300.11 NEC
3) FLEX OR MC NOT TO LAY ON GRID
4) OK WALLS SERVER ROOM 1ST FLOOR