Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2011 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 08/25/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SUPPORT MC 12" & 6' PER NEC, EMT WITHIN 3' PER NEC |
|
| 08/19/2011 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELED PER CONTRACTOR |
|
| 08/05/2011 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LV CABLING TO BE SUPPORTED 725-800 NEC 2) 2 X 4 AND ANY LAY IN FIXTURES NEED TO BE SECURED TO GRID 300.11 NEC 3) FLEX OR MC NOT TO LAY ON GRID 4) OK WALLS SERVER ROOM 1ST FLOOR |