Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2011 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 06/30/2011 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/27/2011 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) DWV FOR TOILET, TEST OK 2) MAKE CONNECTION AND LEAVE OPEN FOR INSPECTION INSTALL WRAPS 3) SINK TRAP ARM, 1 1/2" IS LIMITED TO 42" AND ALSO PROVIDE SUPPORTS 4) DOMESTIC WATER NOT SIZED PER PLAN, CONNECT TO 3/4" SUPPLY MIN. INSTALL SOVE AS SHOWN 5) ALL JOINTS BELOW FLOOR REQUIRE BRACING 6) ISOLATE PIPING FROM METAL, PROVIDE SAFETY PLATES FOR SEPERATION OF HOT AND COLD 7) DW SOV REQUIRES ACCESS 8) LAV CARRIER SPECIFIED 9) DO NOT COVER ANY PLUMBING |