Permit: T11CM01699

Parcel: 13707034B

Inspection Status: Approved

Inspection History: PLUMBING - ABOVE CEILING

Date Description Inspector Results Comments
10/14/2011 PLUMBING - ABOVE CEILING Approved
09/16/2011 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) VENT THRU ROOF RED LINE ON SITE FOR EXAM #126 OK
09/09/2011 PLUMBING - ABOVE CEILING Not ready for Inspection 1) MINIMUM SIZE VENT FOR BACK TO BACK SINKS IS 1 1/2" ONLY
2) 1/3 OF THE TOTAL DEVELOPED LENGTH OF A VENT MAYBE RUN IN THE HORIZONTAL POSITION MAX LENGTH FOR 1 1/2" VENT IS 60', ONLY 20' CAN BE RUN HORIZONTAL
07/21/2011 PLUMBING - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) ABOVE CEILING TO WATER HEATER AREA AND WEST FROM IT OK